VV300 Priority Valve

VV300 priority valves are a combination between pressure regulating and pressure limiting valves. They are used to ensure priority drinking water supply to important systems. Ancillary systems are then supplied only when there is sufficient surplus drinking water available. In addition downstream installations are protected against excess supply pressures. The compact construction makes them particularly suitable for applications where space is limited, for example in ducts. The application of priority valves prevents pressure damage. The set pressure remains constant even when the inlet pressure fluctuates greatly.

 

  • Opening pressure, pilot valve CX-PS 1 - 12 bar.
  • Outlet pressure, pilot valve CX-PR 1 - 12 bar.
  • High flow capacity
  • High control accuracy
  • Powder coated inside and outside - Powder used is physiologically and toxicologically safe
  • Integral control circuit and ball valves

 

Housing with flange, PN 16, ISO 7005, EN 1092-2; PN 25 on request

 

DN size (mm)Flow capacity KvsType
50 43 VV300-50A
65 43 VV300-65A
80 103 VV300-80A
100 167 VV300-100A
150 407 VV300-150A
200 676 VV300-200A
250 1160 VV300-250A
300 1600 VV300-300A
350 1600 VV300-350A
400 3300 VV300-400A
450 3300 VV300-450A
BIM Downloads